® | Oil regeneration system |
|
about plant
|
|
UVM-R-0.7 |
The UVM-R-0.7 system serves for full regeneration and improving of transformer oil’s acid number by means of adsorbent of electrical insulating oil, viscosity of which does not exceed 70 cSt at temperature 50°C. The system restores oil to its virgin properties. The system is able to effectively remove contaminants such as acids and sludge from the oil as well as rectifying the color and restoring oxidation stability of the oil.
The system is used while installation, repair and operation of oil-filled high-voltage equipment up to 1150 kV (power transformers, high-voltage switches etc.). Terms of application - ambient temperature from 283 to 308 K (+10°C – +35°C) - atmospheric pressure from 84 to 106.7 kPa - height above sea level up to 2000m - fire and explosion proof room |
| ¹ | Specification | Value | |
|
UVM-R-0.7 |
|||
| 1 | Capacity, m³/hr | 0.7 | |
| 2 | sorbent consumption, % out of oil weight | 4-6 | |
| 3 |
sorbent’s one-time load, kg |
50 | |
| 4 | Oil’s temperature, °C | 80 | |
| 5 | Power of oil heater, kW | 60 | |
| 6 | Oil heater mean surface power, W/cm³ | 1.1 | |
| 7 | Power consumption, kW | 67 | |
| 8 | Three phase VAC, 50/60 Hz, V | 380 | |
| 9 |
Dimensions, mm :
- length - width - height |
2100 1100 2100 |
|
| 10 | Weight, kg | 1000 |
| Press-filter | ||
press-filter |
Dimensions, mm
- length - width - height Weight, kg |
2400 1000 845 915 |
| products | home | contacts |